TYH SERIES COOLING TOWER – is an induce draft vertical discharge type, cross-flow (double flow) film filled. The performance of TYH Series has been certified by CTI in accordance with CTI Standards STD-201. It shall be designed with high efficiency and minimum maintenance.
The casing ,cold water basin are made of Fiberglass reinforce Polyester (FRP) and two side smooth
The cooling tower main frame structure shall Hot Dip Galvanized Steel(HDGS.)
Fan shall be axial flow type with aerofoil aluminum fan blades designed to provide the necessary airflow for heat transfer. The aerodynamic shape together with low tip speed ensure a lower noise level and low power consumption. The fan are adjustable for in pitch.
- The efficiency of the cooling tower depends upon the ability of the fill to promote both maximum contact surface ,and the maximum contact time between air and water
- This fill is thermally vacuum formed from rigid polyvinyl chloride(PVC). PVC material complies to CTI code STD-136 Standard and UV protected .The fill will be able to withstand temperature of up to 55 0C and surface burning with a flame spread rating less than 25 per ASTM E-84
- -Integral drift eliminator and inlet louver keep circulation water confined to fill over a wide range of flowrate.The TYH series incorporate TCI-75X fill with its triple-pass design is of limiting drift loss to less than 0.005% of the design flowrate
- Gravity flow distribution system.Easy,nonrestrictine maintenance
- Target Nozzle are essential to ensure proper distribution of water over the fills. The TYH series uses the Spiral Target Nozzle which provides maximum thermal performance.
- The TYH Series employs as standard belt and pulley drive system.The configuration of the drive system is simple and easy to maintain.
- The TYH Series provide HW Basin cover made of FRP (an excellent non-corrosive material)
- The TYH Series provide handrail are standard item for safety
- HDGS steel internal piping all flanges are per ANSI 150
Option:
- Stainless Steel Structure (SUS304 or SUS316) available under special conditions.
- Gearbox Drive Option in Lieu of Belt Drive System is readily available for cooling Tower that requires rugged and continuous operation.
- Vertical Gear Drive Option in Lieu of Belt Drive System is readily available for cooling Tower that requires rugged and continuous operation.